Environmental Science & Engineering - www.esemag.com - September 2005
Comments? send them to the editor.
Eliminating harmonics improves productivity and reliability at wastewater treatment plant
Power electronic loads such as
drives, ozone generators and
UV filtration equipment have
become abundant in the water
and wastewater treatment industries
due to their many benefits. But they
have one major drawback in common:
they might produce a problematic condition
known as harmonics. The
Corvallis, Oregon Water Reclamation
Facility fell victim to harmonics, but
found a solution in a power correction
system from Schneider Electric.
The term harmonics is used to
describe a component of a periodic
voltage or current waveform having a
frequency that is an integral multiple
of the fundamental power line frequency,
60Hz in the U.S. This irregular
waveform results because the waveform
required by power electronic
loads is quite different than the sinusoidal
voltage delivered by the utility.
This ‘non-linear’ current draw results
in a distorted waveform.
High levels of harmonic distortion
can stress the electrical network within
a water treatment facility and on the
servicing utility, causing problems for
sensitive electronic equipment. The
impact on a facility can be very costly,
especially when processes are disrupted
or shut down, reducing productivity,
increasing repair and maintenance
costs, and possibly spilling partially
treated or untreated wastewater into
nearby waterways.
Besides cleanup costs, which can
run into the millions, in the US,
Environmental Protection Agency
imposed fines are extremely harsh for
sewage spills, and the impact of such a
spill on the health of local wildlife and
people can be substantial.
Warning symptoms of problematic
harmonic levels include overheating
motors, drives and cables, thermal tripping
of protective devices and logic
faults of digital devices (CNC, PLC,
computers) and generator faulting, all
of which can result in process downtime.
These warning symptoms began at
the Corvallis facility after a major
upgrade that included four new influent
pumps, new distribution equipment
and a SCADA system to provide overall
control, data collection and plant
performance documentation. Variable
frequency drives (VFD) were chosen
as the most efficient means for controlling
the two new pumps.
After completion of the equipment
installation, commissioning progressed
smoothly until the last of the
new equipment, the SCADA system,
was brought on line. The facility managers
were immediately plagued with
considerable downtime due to logic
faults in the SCADA system, nuisance
tripping of ground fault circuit breakers,
frequent activation of zero
sequence relays in the LV switchgear,
and random and autonomous switching
of the influent control gates.
The plant reverted to manual control
but the faults – although less frequent
– continued. Operators then
noted that these problems seemed to
increase when two or more drives were
operating on a common MCC bus at
one time.
- Ground fault trips occurred when
the speed of the pumps was changed.
- Ground fault breakers tripped
when the VFD was started or stopped.
- Influent pump gates switched
when the speed was changed.
- Negative sequence relays activated
when the speed was changed.
Facility managers hired an independent
test service to analyze the
problems. They measured harmonic
voltage and current distortion, current
and voltage transients during acceleration
and deceleration of the pumps,
control signals, zero sequence current
during speed changes, and neutral to
ground voltage in the breakers. The
harmonic voltage and current distortion
were measured at varying carrier
frequencies to determine if such
changes affected the harmonic conditions.
The tests indicated that:
- There was no measurable difference
in the line harmonics when the
carrier frequency was changed from
4.5 kHz to 1.5 kHz.
- The total harmonic current distortion
[THD (I)] level measured at
89% output speed (approximately 95%
load) of one VFD was 38.8% with the
5th order and 7th order having the
highest amplitude. Note that each VFD
had 3% impedance line reactors.
- The total harmonic voltage distortion
[THD (V)] measured 3.8%.
- A high frequency noise, very
close to that of the VFD carrier frequency,
appeared on the 4-20 mA DC
gate signal when the VFD was accelerated,
decelerated, started or stopped.
These noise impulses caused the gate
to adjust position.
- The zero sequence (neutral) current
and voltage (208/120Y V) were
sensitive to changes in the carrier frequency.
As the carrier frequency
increased from 1.5kHz to 4.5kHz, the
zero sequence current increased from
2mA to 400 mA. This corresponded to
a dramatic increase in the incidence of
breaker trips.
- Notably, a high frequency, consistently
seven times that of the carrier
frequency, existed in the zero sequence
current waveform.
After several remedies were suggested
and implemented, the problems
occurred less frequently but were not
entirely eliminated.
Fifteen months passed before a local
electrical distributor working with the
Corvallis facility contacted the power
quality specialists at Schneider
Electric’s plant in Salem, Oregon.
Several members of the AccuSine
Active Harmonic filter team met with
representatives of the facility, toured
the plant and reviewed test data.
The team noted several likely contributors
to the problems. First, cables
of VFD are broadcast antennae for
high frequency noise that can radiate
to other cables in the same vicinity. All
cables act like receiving antennae for
this high frequency noise and low voltage
control wiring is highly susceptible.
As a result, the low voltage signals
are easily corrupted. To protect control
wiring from this noise, it should never
be installed running parallel to VFD
power cabling even if each set of
cables is in a separate metal conduit. In
fact, the only time that VFD power
cables should come close to control
cables is when they cross at 90
degrees. Because of this, the team recommended
that the power cables be
installed in grounded metal conduit
separate from the control wiring.
Second, a review of the harmonics
test data for the facility revealed that
THD (V) exceeded 5% when two VFD
were operating on one bus, and the
TDD (total demand distortion) exceeded
IEEE 519-1992 recommended limits
of 20% for this installation.
A THD (V) that exceeds 5% can
affect many different types of equipment
– often, electronic equipment –
in an electrical network. The fact that
the SCADA tripped occasionally suggested
that high THD (V) was
involved.
To reduce the levels of TDD within
the guidelines of IEEE 519-1992 and
THD (V) to less than 5%, the team recommended
an AccuSine PCS active
harmonic filter rated at 50 amperes.
After the AccuSine unit was
installed and the power cables rerouted
through grounded metal conduit, the
performance and reliability of the
plant electrical system were greatly
improved. The TDD was measured in
the 5-7% range for one VFD and 18-
21% range for two VFD. The THD (V)
was less than 5% for all circumstances.
The damaging effects of harmonics
should be considered during the design
of a power electronic system. Proper
installation techniques and harmonic
mitigation equipment can eliminate
problems before they occur. From an
economic and performance standpoint,
active filters are often the best choice
for harmonic filtering when compared
to such alternatives as passive filters or
18 pulse drives. With active filters, an
engineer can review a group of loads
easily and accurately in the design
stage without having to perform any
expensive harmonic studies. Standards
compliance can be guaranteed and the
potentially costly problems are avoided.
The Corvallis case shows how harmonics
can disrupt water and wastewater
treatment processes, driving up
costs. This troubling power issue
should be considered during the design
stage of a project. Research your many
options in harmonic mitigation equipment
to find the most cost effective
and reliable solution for your facility.
For more information please
contact Eric Truesdale at
etruesdale@bader-rutter.com
See our home page on how to order your subscription. We regret we can
only accept orders from Canada.